Central HVAC systems
T
T
T P
T
M
P T
T
+
T
ΔP
ΔP ΔP
M02
ΔP
ΔP
M
B01
Y02
B11
F14_3 F14_2 F04
F04
Y22
Y20
Y102
Y101Y01
F14_1
M06
M02
M01
B09
F1
BD1 B03
B04 BD2 B06
HVAC system
HVAC system
Product Description
CX5010-1111 TwinCAT PLC, Windows CE
- CX1800-1052 Windows CE, BACnet image *
- CX1900-0025 2 GB CF-Card instead of 64 MB *
KL1809 16-channel digital input 24 V DC
M01_2
M01_3
M01_5
M02_2
M02_3
M02_5
M06_2
M06_3
Y01_2
Y02_2
Y102_2
F1
Supply air frequency converter fault signal
Supply air frequency converter operating signal
Supply air repair switch
Exhaust air frequency converter fault signal
Exhaust air frequency converter operating signal
Exhaust air repair switch
Preheating pump operating signal
Preheating pump fault signal
Ambient air gate stop position OPEN
Exhaust air gate stop position OPEN
Heat recovery bypass gates stop position OPEN
Antifrost thermostat
KL3208-0010 PT1000 8-channel analog input
B01
B03
B04
B06
B09
B000
Ambient air temperature
Supply air temperature
Exhaust air temperature
Room temperature
Preheater return temperature
Exhaust air temperature
KL9186 Potential distribution terminal 24 V DV
KL9187 Potential distribution terminal 0 V DV
KL3468 8-channel analog input 0…10 V
F03
F04
F14_1
F14_2
F14_3
BD1
BD2
Supply air differential pressure sensor
Exhaust air differential pressure sensor
Ambient air fi lter differential pressure sensor
Exhaust air fi lter differential pressure sensor
Heat recovery differential pressure sensor
Supply air pressure
Exhaust air pressure
KM2652 2-channel relay module 230 V AC, 6 A, manual/automatic
operation
M01_1
M02_1
M06_1
Y01_1
Y02_1
Supply air frequency converter clearance
Exhaust air frequency converter clearance
Preheating pump clearance
Ambient air gate
Exhaust air gate
KM4602 2-channel analog output 0…10 V, manual/automatic
operation
M01_4
M02_4
Y102_1
Y20
Y22
Supply air VFD target setting
Exhaust air VFD target setting
Heat recovery bypass gates
Preheater control valve
Cooling control valve
KL9010 End terminal