Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS
4
Remote Slab/Outdoor Temperature Sensor: CHV-RSS Installation Guide – DOC. 6229D
Setup
Tile or Wood Floor Installation
Crestron recommends the sensor be placed inside a 1/2 inch (13 mm)
Electrical Metallic Tubing (EMT) conduit. This allows future sensor
replacement, if required. The radius of the bend at the wall should be
approximately 8 inches (203 mm), to allow for removal and replacement
of the sensor.
Sensor Position (Side View)
NOTE: Ensure the sensor conduit is vertically centered in the slab below
the surface.
Sensor Conduit Position in Slab
For indoor installations, consider the following:
• In small rooms, position the sensor near the center of the floor.
• In larger rooms, ensure the sensor is at least 6 feet (1.8 meters)
from the wall.